Context Plus ZFP range is a fire panel that is touchscreen-controlled, a breeze to install, provides clear and constant feedback on all aspects of system activity and is fully compliant with all relevant standards. The ZFP – a powerful, intuitive and feature-rich range of 1 to 8 loop addressable fire panels from Context Plus.
POWER SUPPLY & CHARGER | |
Mains Supply Operating Voltage |
230VAC ± 10% 50/60Hz 810mA max.
|
Rated Current |
810mA Max (Standard cabinet ZFPs; 1.35A Max (Medium & Large Cabinet ZFPs)
|
Mains Supply Operating Voltage |
5A (Standard cabinet ZFPs); 5A(Medium & Large Cabinet)
|
Max. Continuous Output current (incl. charging) |
5A (Standard cabinet ZFPs); 5A(Medium & Large Cabinet)
|
Max. VRLA Battery Size and Type |
2 x 12V 18Ah (Standard cabinet ZFPs); 2 x 12V 38Ah (Medium & Large Cabinet)
|
LOOP DRIVERS | |
Number of loops |
1, 2, 4, 6 or 8 dependent on model
|
Max. Output Current per Loop |
500mA (Voltage: 25V min; 34V max)
|
Communication Protocol |
Context Plus XP95 (max. 127 addressable devices per loop)
|
Type of Cable/Max. cable length per loop |
Fire resistant screened, up to 2.5mm2 /1KM max length
|
Max. allowable loop impedance/capacitance |
20 ohm (each conductor)
|
Max. cable capacitance | .27uF |
CONVENTIONAL SOUNDER CIRCUITS | |
Number/Type of Conventional Sounder Circuits |
2 x 1A output. Protected by resettable overload circuit 19.5V min; 28V max.
|
Output Voltage |
19.5V minimum, 28V maximum
|
Type of Cable/Max. cable length per loop |
Fire resistant screened, up to 2.5mm2 /1KM max length
|
AUXILIARY INPUTS (PROGRAMMABLE) | |
Numbers of Auxiliary Inputs |
2 (Connect to 0V to trigger, Max. input voltage 27VDC non-latching).
|
EOL resistor value (supplied) |
6800 ohm, 5%Tol, 0.25W 6800 ohm, 5% tolerance, 0.25W
|
Trigger Resistor (supplied) | 470R, 0.25W |
RELAY OUTPUTS (PROGRAMMABLE) | |
Number of Relay Outputs |
2 x programmable auxiliary relays; 1 x failsafe fault relay; 1 x 24VDC auxiliary power output
|
Relay Type & Outputs |
1A, 30VDC (maximum). Voltage free, single pole changeover
|
Fault Relay |
Active when faults are present or on total power failure
|
24VDC Auxiliary Power Output |
19.5V minimum, 28V maximum. Max current 100mA
|
INDICATORS AND CONTROLS | |
Standard Provision |
All models include a Z41 Control module which comprises a full colour 4.3” touchscreen.
All mandatory EN54 indicators, 3 spare LEDs & a keyswitch allowing access to AL2 |
Zonal Indicators |
Up to 200 programmable LEDs available via Switch & Indicator expansion modules cabinets);
|
Switches & Onboard Printers |
Multiple switch & printer configs available via Switch & Indicator expansion modules
|
Switch & Indicator Module Capacity |
2 (standard cabinets); 4 (medium cabinets); 6 (large cabinets). 1 x Z41 req. per panel
|
COMMUNICATION BUSES | |
On-Board Serial Printer (Optional) | 1 x RS232 connector |
Pager/DECT Interface | 1 x RS232 connector |
Networking |
1 x RS485 connector (hi-intergrity fault-tolerant)
|
Peripheral Bus (A-Bus) |
1 x RS485 connector. Allows the connection of up to 15 A-Bus PCBs.
Wiring requirements = 2 core plus screen plus 2 core for power. |
PC Interface |
Galvanically isolated USB connector (provided on the Z41 Control/Display module)
|
NETWORKING | |
Network Type |
1 x RS485 connector (hi-intergrity fault-tolerant, ring wired). 1xZHN PCB required per networked panel
|
Maximum no. of Network Nodes |
128 (up to 64 x 8 loop panels and 64 x compact controllers)
|
Type of Cable/ Max. Cable Length |
Fire resistant screened, up to 2.5mm2 /1KM between nodes; 128KM (max network length)
|
Network Wiring |
Fire resistant screened cable, up to 2.5mm2
|
Detail |
Events (Fires, Faults, Disablements, Tests) & Actions (Silence/Resound Sounders, Reset) can be accepted over the network. Zones, Input & Output Groups, etc cab be shared over the network
|
MECHANICAL & ENVIRONMENTAL | |
Finish & IP Rating |
Light Grey texture (RAL7035) epoxy. Mild steel. Zintec 1.2mm
|
Operating Temperature/Humidity |
-5°C to + 40°C / 5% to 95% R.H non condensing
|
Dimension (H x W x D) mm |
462 x 450 x 200 (Standard); 720 x 450 x 200 (Medium); 960 x 450 x 200 (Large); 178 x 214 (Compact Controller)
|